All caught attacksAttack walkthrough / evidence trace / WaDi 2017

Attack #162LIT002

Elevated-reservoir tank level transmitter. Attacker's intended impact: Stealthy attack.

Single Stage, Single PointWater Distribution10m 35s windowfirst catch 4m 43s1 of 1 engines flagged it
1.0Plant

Where it hit the plant

P1

primary grid, raw-water intake & dosing

P2

elevated reservoir, secondary distribution

2LIT002
P3

consumer / return network

2.0Timeline

Attack window and detections

Labelled window2017-07-11 15:26:30 to 2017-07-11 15:37:00plant local time
Physical Residual
4m 43s

Shaded band: the labelled attack window from the iTrust ground-truth catalog. Marks: the first second each engine flagged the window. "No flag" means the engine stayed silent for the whole window.

3.0Evidence

Why it was flagged

At 2017-07-11 15:26:30, attack #16 (SSSP) manipulated 2LIT002 — “Overflow of Elevated Reservoir tank”. The serving model raised the alert 283 seconds after onset (peak score 1.0596x the operating threshold). The dominant physical evidence: 2MV006 — motorized valve, Stage 2 (elevated reservoir — secondary distribution) was driven to a state the plant's learned physics did not predict from the rest of the process, carrying 7% of the anomaly score — 10.5x its share in normal operation. Supporting deviations were concentrated in 2P003, 2P003SPEED, 1AIT003. In plain terms: the plant's own physics stopped agreeing with what the sensors were reporting, in exactly the part of the process the attacker touched.

From the official explain run 2026-06-14T18:37:06Z
Peak score 1.06x of the operating threshold

Sensors carrying the anomaly score

SensorShare of scoreDeviationShare vs normal
2MV006
motorized valve, Stage 2 (elevated reservoir — secondary distribution)
6.6%5.5σ10.5x
2P003
pump, Stage 2 (elevated reservoir — secondary distribution)
6.5%5.3σ8.5x
2P003SPEED
pump, Stage 2 (elevated reservoir — secondary distribution)
5.0%4.1σ5.5x
1AIT003
water-quality analyzer, Stage 1 (primary grid — raw-water intake & dosing)
4.8%4.0σ2.7x
1AIT005
water-quality analyzer, Stage 1 (primary grid — raw-water intake & dosing)
3.9%3.2σ1.9x
2PIT001
pressure transmitter, Stage 2 (elevated reservoir — secondary distribution)
3.7%3.0σ3.0x
2_FIC_401_PV
plant instrument, Stage 2 (elevated reservoir — secondary distribution)
3.1%2.6σ5.1x
2_FIC_501_SP
plant instrument, Stage 2 (elevated reservoir — secondary distribution)
3.0%2.5σ1.5x
4.0Provenance

Every figure has a run.

Validation run

2026-06-13T22:27:18Z, commit de79dac5398150de9bc5eda89a529d2dbb942c6c

Model image

sha-de79dac53981

Metrics artefact SHA-256

a05be50d6a12ad442d292f0b9759d4087430c537fcc3b93712812ff55d5605bb

Explain run

2026-06-14T18:37:06Z

Explain artefact SHA-256

ce5f77ae0bc78a0576ec3ca053b5594844039f7f77c0aa2ba63850a9bf46874f

Generator

vardar-portal/scripts/build-gallery-data.mjs (DEL-34/DEL-43)